Hoshizaki “A Superior Degree of Reliability” www.hoshizaki.com Models KM-1301SAH/3 KM-1301SWH/3 KM-1301SRH/3 Stackable Crescent Cuber Hoshizaki Ame
104. KM-1301SWH3 (water-cooled)Note: We reserve the right to make changes in specications and design without prior notice.AC SUPPLY VOLTAGE 208-230/6
115. KM-1301SRH (remote air-cooled)Note: We reserve the right to make changes in specications and design without prior notice.AC SUPPLY VOLTAGE 208-2
126. KM-1301SRH3 (remote air-cooled)Note: We reserve the right to make changes in specications and design without prior notice.AC SUPPLY VOLTAGE 208-
13B. Condenser Unit1. URC-14FUnit: inches (mm)
14 SPECIFICATIONSMODEL: URC-14FAC SUPPLY VOLTAGE 115/60/1 (Connection to Icemaker) FAN MOTOR 115 V Total 2.6FLA 130WEXTERIOR DIMENSIONS (WxDxH) 35-11
15II. General InformationA. Construction1. KM-1301SAH, KM-1301SAH3 (air-cooled)Evaporator AssemblySpray TubesInlet Water ValveWater Supply InletHot Ga
162. KM-1301SWH, KM-1301SWH3 (water-cooled)Evaporator AssemblySpray TubesInlet Water ValveWater Supply InletHot Gas ValveJunction BoxWater Regulating
173. KM-1301SRH, KM-1301SRH3 (remote air-cooled)Evaporator AssemblySpray TubesInlet Water ValveWater Supply InletHot Gas ValveJunction BoxesReceiver T
18B. Sequence of OperationIMPORTANTThis unit utilizes a thermostatic bin control. For operation, the K4 jumper (4A4883G01) must be in place on the con
19de-energize. For the rst 5 minutes, CB will not accept a signal from F/S. This minimum 5-minute freeze time is short cycle protection for Comp. At
2IMPORTANTOnly qualied service technicians should install, service, and maintain the icemaker. No service or maintenance should be undertaken until t
202. Sequence Flow Chart•WVtime:6min.orthelengthofharvestminus0or50 sec. (S4 dip switch 7), whichever is shorter. DO NOT ADJUST S4 dip s
21C. Control Board•A Hoshizaki exclusive solid-state control board is employed in KM-1301SAH/3, KM-1301SWH/3, and KM-1301SRH/3, Stackable Crescent Cu
221. Control Board LayoutControl BoardPart Number 2A3792-01"G" Control Board"ALARM RESET" Button"OUTPUT TEST" Button(use
232. Featuresa) Maximum Water Supply Period - 6 minutesThe inlet water valve will be open during harvest for 6 minutes or the length of harvest minus
24f) LED Lights and Audible Alarm SafetiesAt startup, a 5-second delay occurs while the control board conducts an internal timer check. A beep occurs
253. Controls and AdjustmentsCAUTIONDip switches are factory set. Failure to maintain factory settings may adverselyaffect performance and warranty co
26c) Pump-Out Timer (S4 dip switch 3 & 4)CAUTIONDo not adjust S4 dip switch 3 off and S4 dip switch 4 on for this model. Otherwise, pump motor doe
27e) Harvest Pump Timer (S4 dip switch 7)CAUTIONFactory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may
28h) Float Switch Control (S5 dip switch 1)CAUTIONDo not adjust. This must be left in the factory default position or the unit will not operate corre
29D. Bin ControlCAUTIONWhen the ambient temperature is below 45°F (7°C), the thermostatic bin control switch opens and shuts down the icemaker even if
3CONTENTSImportant Safety Information ... 6I. Specicati
30III. Technical InformationA. Water Circuit and Refrigeration Circuit1. KM-1301SAH, KM-1301SAH3 (air-cooled)Water SupplyCleaning ValveFloat SwitchDra
312. KM-1301SWH, KM-1301SWH3 (water-cooled)Water SupplyCleaning ValveFloat SwitchDrainCheck ValveExpansion ValvesCompressorHot Gas ValveCheck ValvesHi
323. KM-1301SRH, KM-1301SRH3 (remote air-cooled)Water SupplyCleaning ValveFloat SwitchDrainCheck ValveExpansion ValvesCompressorHot Gas ValveCheck Val
33B. Wiring Diagrams1. Auxiliary Code T-0, U-0 a) KM-1301SAH (air-cooled)Auxiliary Code T-0, U-0Transformer Output 10.5V at 115V** High Pressure Switc
34b) KM-1301SWH (water-cooled)Auxiliary Code T-0, U-0*Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 384±21 PSIG Cut-in 284±21 PSIG0
35c) KM-1301SRH (remote air-cooled)Auxiliary Code T-0, U-0Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 412±21 PSIG Cut-in 327±21 PSIG
36d) KM-1301SAH3 (air-cooled) and KM-1301SWH3 (water-cooled)Auxiliary Code T-0, U-0Transformer Output 10.5V at 115V** High Pressure SwitchAir-Cooled M
37e) KM-1301SRH3 (remote air-cooled)Auxiliary Code T-0, U-0*Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 412±21 PSIG Cut-in 327±21 PS
382. Auxiliary Code U-1 and Later a) KM-1301SAH (air-cooled) Auxiliary Code U-1 and LaterTransformer Output 10.5V at 115V** High Pressure SwitchCut-ou
39b) KM-1301SWH (water-cooled) Auxiliary Code U-1 and Later*Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 384±21 PSIG Cut-in 284±21 P
4e) Harvest Pump Timer (S4 dip switch 7) ... 27f) Factory Use (S4 dip switch 8) ...
40c) KM-1301SRH (remote air-cooled)Auxiliary Code U-1 and Later*Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 412±21 PSIG Cut-in 327±2
41d) KM-1301SAH3 (air-cooled) and KM-1301SWH3 (water-cooled)Auxiliary Code U-1 and Later*Transformer Output 10.5V at 115V* High Pressure SwitchAir-Coo
42e) KM-1301SRH3 (remote air-cooled)Auxiliary Code U-1 and Later*Transformer Output 10.5V at 115V* High Pressure SwitchCut-out 412±21 PSIG Cut-in 327±
43C. Performance Data1. KM-1301SAH (air-cooled)Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used
442. KM-1301SAH3 (air-cooled)Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference onl
453. KM-1301SWH (water-cooled) Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference o
464. KM-1301SWH3 (water-cooled) Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference
47Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for reference only.2. We reserve the right t
486. KM-1301SRH3 (remote air-cooled)Note:1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold should be used for refere
49IV. Service Diagnosis WARNING1. This unit should be diagnosed and repaired only by qualied service personnel to reduce the risk of death, electric
5V. Removal and Replacement of Components ... 65A. Service for Refrigerant Lines ...
503) 1-Minute Fill Cycle – LED 4 is on. WV and X2 relay (auxiliary code T-0, U-0), X11 relay (auxiliary code U-1 and later) energize and the 1-minute
515) Freeze Cycle – LED 1 is on. Comp and FMR remain energized, PM energizes or remains energized depending on harvest pump timer (S4 dip switch 7) se
52Diagnosis: If PM does not reverse, check to see if CB S4 and S5 dip switch settings are in the factory default position. If S4 dip switch 3 and 4 ar
53B. Control Board CheckBefore replacing a control board that does not show a visible defect and that you suspect is bad, always conduct the following
54C. Bin Control CheckTo check the thermostatic bin control, follow the steps below.CAUTIONWhen the ambient temperature is below 45°F (7°C), the therm
558) Reconnect the black oat switch connector to the control board BLACK K5 connector, then replace the control box cover in its correct position.9)
567) Wipe down the oat switch assembly's housing, shaft, oat, and retainer rod with a mixture of 1 part Hoshizaki "Scale Away" and 25
57F. Diagnostic Charts1. No Ice ProductionProblem Possible Cause Remedy[1] The icemaker will not start.a) Power Supply 1. Off, blown fuse, or tripped
58Problem Possible Cause Remedy[1] The icemaker will not start. (continued)h) Transformer 1. Coil winding open or shorted.1. Replace.i) Wiring to Cont
59Problem Possible Cause Remedy[3] Compressor will not start or stops operating.a) Magnetic Contactor 1. Bad contacts. 1. Check for continuity and rep
6Important Safety InformationThroughout this manual, notices appear to bring your attention to situations which could result in death, serious injury,
60Problem Possible Cause Remedy[7] Fan motor will not start, or is not operating (except water-cooled model).a) Fan Motor 1. Motor winding open. 1. Re
61Problem Possible Cause Remedy[1]Freeze cycle time is too long. (continued)f) Thermistor 1. Loose or disconnected.1. Reattach or connect. See "I
62Problem Possible Cause Remedy[3]Other. a) Ice Cube Guide 1. Out of position. 1. Place in position.b) Thermostatic Bin Control 1. Bulb out of positi
63Problem Possible Cause Remedy[2] Harvest cycle time is long.a) Water Supply 1. Water temperature too cold.1. Increase temperature.b) Thermistor 1. O
64Problem Possible Cause Remedy[2] Cloudy or irregular cubes.a) Evaporator 1. Frozen up. 1. See chart 2. 2. Scaled up. 2. Clean3. Damaged. 3. Replace
65V. Removal and Replacement of Components WARNING1. This unit should be diagnosed and repaired only by qualied service personnel to reduce the risk
662. Brazing WARNING1. R-404A itself is not ammable at atmospheric pressure and temperatures up to 176°F (80°C).2. R-404A itself is not explosive or
673) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity.4) Close the low-side valve and high-sid
687) Remove the compressor. Unpack the new compressor package. 8) Attach the rubber grommets of the prior compressor to the new compressor.9) Place th
698) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detecto
7I. SpecicationsA. Icemaker1. KM-1301SAH (air-cooled)Note: We reserve the right to make changes in specications and design without prior notice.AC S
7010) Evacuate the system, and charge it with refrigerant. For air-cooled and water-cooled models, see the nameplate for the required refrigerant char
71F. Removal and Replacement of Air-Cooled CondenserCAUTION1. Always install a new drier every time the sealed refrigeration system is opened. 2. Do n
72G. Removal and Replacement of Water-Cooled CondenserCAUTION1. Always install a new drier every time the sealed refrigeration system is opened. 2. Do
73H. Removal and Replacement of Remote Air-Cooled CondenserCAUTION1. Always install a new drier every time the sealed refrigeration system is opened.
74I. Removal and Replacement of Water Regulating Valve (water-cooled model)CAUTION1. Always install a new drier every time the sealed refrigeration sy
7518) Check for water leaks.19) Replace the panels in their correct positions.20) Turn on the power supply.J. Adjustment of Water Regulating Valve (wa
768) Braze all ttings with nitrogen gas owing at a pressure of 3 to 4 PSIG. 9) Use an electronic leak detector or soap bubbles to check for leaks. A
7711) Connect the white thermistor connector through the bushing of the control box to the control board WHITE K3 connector.CAUTIONDo not cut the lead
7810) Turn on the power supply.11) Check for leaks.12) Replace the front panel in its correct position.13) Turn on the power supply.O. Removal and Rep
79P. Removal and Replacement of Control BoardWhen replacing a control board follow the precautions below.CAUTION1. The control board is fragile; handl
8Note: We reserve the right to make changes in specications and design without prior notice.2. KM-1301SAH3 (air-cooled)AC SUPPLY VOLTAGE 208-230/60/3
80CLOSED POSITION OPEN POSITIONVI. Cleaning and MaintenanceIMPORTANTEnsure all components, fasteners, and thumbscrews are securely in place after any
811. Cleaning Procedure1) Dilute 27 . oz. (800 ml) of Hoshizaki "Scale Away" with 5 gal. (19 l) of warm water. 2) Remove all ice from the e
8218) Replace the front panel in its correct position.19) Turn on the power supply to ll the water tank with water.20) Turn off the power supply afte
83B. Maintenance InstructionsIMPORTANTThis icemaker must be maintained individually, referring to the instruction manual and labels provided with the
845) Open the water regulating valve by using a screwdriver to pry up on the spring retainer underneath the spring. While holding the valve open, blow
93. KM-1301SWH (water-cooled) Note: We reserve the right to make changes in specications and design without prior notice.AC SUPPLY VOLTAGE 208-230/60